When using the mSupply ColdChain application for the first time, the Sensor Settings screen will have two sections: | When using the mSupply ColdChain application for the first time, the Sensor Settings screen will have two sections: | ||
*Options | *Options | ||
- | *Found Sensors | + | *Found Sensors |
+ | <WRAP center round important 60%> Please refer to the [[en: | ||
=== Options === | === Options === | ||
- | **Logging interval:** Sets the default number of minutes between logs on sensors. Using the slider, you can set the default log interval to any length between 1 and 100 minutes. The logging interval applies for all sensors when they are first linked to the mSupply ColdChain application. Different log intervals can be set for each sensor in **'' | + | **Logging interval:** Sets the default number of minutes between logs on sensors. Using the slider, you can set the default log interval to any length between 1 and 100 minutes. The logging interval applies for all sensors when they are first linked to the mSupply ColdChain application. Different log intervals can be set for each sensor in **Available Sensors/Log interval** |
{{ : | {{ : | ||
Line 32: | Line 33: | ||
{{ : | {{ : | ||
- | <WRAP center round tip 60%>We recommend | + | <WRAP center round tip 50%>We recommend you avoid the use special characters |
- | **Log interval:** Using the slider, you can set the interval between logs to any length between 1 and 30 minutes. When you press '' | + | **Log interval: |
{{ : | {{ : | ||
- | <WRAP center round info 60%> The log interval will initially be set to the default log interval. </ | ||
+ | ==== Temperature breach settings ==== | ||
+ | There are two breach categories: | ||
+ | ***Single Exposure:** any continuous period of time the temperature is outside the specified range. | ||
+ | ***Cumulative Exposure:** the sum of time the temperature is outside the specified range during a period. | ||
+ | Temperature breach settings apply to all sensors. | ||
+ | {{ : | ||
+ | === Single exposure breach configurations === | ||
+ | You should set a minimum temperature (cold breach) and maximum temperature (hot breach) for the single exposure breaches. The current setting will be displayed in the row for each category. | ||
- | Note: We recommend | + | **Description:** The default names for the two single exposure breach configuration are: |
+ | *Hot breach | ||
+ | *Cold breach | ||
+ | However, you can enter a custom name for each temperature breach category if required. | ||
+ | {{ : | ||
+ | <WRAP center round tip 50%>We recommend | ||
+ | **Duration: | ||
+ | {{ : | ||
+ | <WRAP center round important 50%>The duration should be equal or greater to the log interval. The duration should also be a multiple of the log interval to ensure breaches are captured accurately.</ | ||
+ | **Temperature: | ||
+ | *below which will be a breach for the cold breach category, and | ||
+ | *above which will be a breach for the hot breach category. | ||
+ | {{ : | ||
+ | The temperature selected can be between -30 and +50 degrees Celsius. | ||
+ | |||
+ | |||
+ | === Cumulative Exposure Configurations === | ||
+ | You should set a minimum temperature (cold breach) and maximum temperature (hot breach) for the cumulative exposure configuration. The current setting will be displayed in the row for each category. | ||
+ | |||
+ | **Description: | ||
+ | *Hot cumulative | ||
+ | *Cold cumulative | ||
+ | You can enter a name for each temperature breach category. | ||
+ | {{ : | ||
+ | <WRAP center round tip 50%>We recommend you avoid the use special characters (e.g. -, +, *) when naming breach categories. </ | ||
+ | |||
+ | **Duration: | ||
+ | {{ : | ||
+ | **Temperature: | ||
+ | *below which will be a breach for the cold breach category, and | ||
+ | *above which will be a breach for the hot breach category. | ||
+ | The temperature selected can be between -30 and +50 degrees Celsius. | ||
+ | {{ : | ||
+ | **Period:** The time period used for cumulative temperature configuration (and hence alerts) on the Sensor tab is set at 72 hours. | ||
+ | |||
+ | To view cumulative temperature breaches for a different period, you can [[en: | ||
+ | |||
+ | <wrap center round info 95%> You can export the sensor logs for further information and investigation regarding temperature breaches. </ | ||
+ | \\ | ||
+ | \\ | ||