Differences
This shows you the differences between two versions of the page.
| Both sides previous revision Previous revision Next revision | Previous revision | ||
| en:cold_chain:settings [2021/02/15 22:03] – rowena | en:cold_chain:settings [2021/06/04 05:49] (current) – [Cumulative Exposure Configurations] Craig Drown | ||
|---|---|---|---|
| Line 8: | Line 8: | ||
| When using the mSupply ColdChain application for the first time, the Sensor Settings screen will have two sections: | When using the mSupply ColdChain application for the first time, the Sensor Settings screen will have two sections: | ||
| *Options | *Options | ||
| - | *Found Sensors | + | *Found Sensors |
| + | <WRAP center round important 60%> Please refer to the [[en: | ||
| === Options === | === Options === | ||
| - | **Logging interval:** Sets the default number of minutes between logs on sensors. Using the slider, you can set the default log interval to any length between 1 and 100 minutes. The logging interval applies for all sensors when they are first linked to the mSupply ColdChain application. Different log intervals can be set for each sensor in **'' | + | **Logging interval:** Sets the default number of minutes between logs on sensors. Using the slider, you can set the default log interval to any length between 1 and 100 minutes. The logging interval applies for all sensors when they are first linked to the mSupply ColdChain application. Different log intervals can be set for each sensor in **Available Sensors/Log interval** |
| {{ : | {{ : | ||
| Line 32: | Line 33: | ||
| {{ : | {{ : | ||
| - | <WRAP center round tip 60%>We recommend | + | <WRAP center round tip 50%>We recommend you avoid the use special characters |
| - | **Log interval:** Using the slider, you can set the interval between logs to any length between 1 and 30 minutes. When you press '' | + | **Log interval: |
| {{ : | {{ : | ||
| - | <WRAP center round info 60%> The log interval will initially be set to the default log interval. </ | ||
| + | ==== Temperature breach settings ==== | ||
| + | There are two breach categories: | ||
| + | ***Single Exposure:** any continuous period of time the temperature is outside the specified range. | ||
| + | ***Cumulative Exposure:** the sum of time the temperature is outside the specified range during a period. | ||
| + | Temperature breach settings apply to all sensors. | ||
| + | {{ : | ||
| + | === Single exposure breach configurations === | ||
| + | You should set a minimum temperature (cold breach) and maximum temperature (hot breach) for the single exposure breaches. The current setting will be displayed in the row for each category. | ||
| - | Note: We recommend | + | **Description:** The default names for the two single exposure breach configuration are: |
| + | *Hot breach | ||
| + | *Cold breach | ||
| + | However, you can enter a custom name for each temperature breach category if required. | ||
| + | {{ : | ||
| + | <WRAP center round tip 50%>We recommend | ||
| + | **Duration: | ||
| + | {{ : | ||
| + | <WRAP center round important 50%>The duration should be equal or greater to the log interval. The duration should also be a multiple of the log interval to ensure breaches are captured accurately.</ | ||
| + | **Temperature: | ||
| + | *below which will be a breach for the cold breach category, and | ||
| + | *above which will be a breach for the hot breach category. | ||
| + | {{ : | ||
| + | The temperature selected can be between -30 and +50 degrees Celsius. | ||
| + | |||
| + | |||
| + | === Cumulative Exposure Configurations === | ||
| + | You should set a minimum temperature (cold breach) and maximum temperature (hot breach) for the cumulative exposure configuration. The current setting will be displayed in the row for each category. | ||
| + | |||
| + | **Description: | ||
| + | *Hot cumulative | ||
| + | *Cold cumulative | ||
| + | You can enter a name for each temperature breach category. | ||
| + | {{ : | ||
| + | <WRAP center round tip 50%>We recommend you avoid the use special characters (e.g. -, +, *) when naming breach categories. </ | ||
| + | |||
| + | **Duration: | ||
| + | {{ : | ||
| + | **Temperature: | ||
| + | *below which will be a breach for the cold breach category, and | ||
| + | *above which will be a breach for the hot breach category. | ||
| + | The temperature selected can be between -30 and +50 degrees Celsius. | ||
| + | {{ : | ||
| + | **Period:** The time period used for cumulative temperature configuration (and hence alerts) on the Sensor tab is set at 72 hours. | ||
| + | |||
| + | To view cumulative temperature breaches for a different period, you can [[en: | ||
| + | |||
| + | <wrap center round info 95%> You can export the sensor logs for further information and investigation regarding temperature breaches. </ | ||
| + | \\ | ||
| + | \\ | ||
| + | | // Previous: | ||
| - | //(The rest of this page is coming soon.)// | ||